Snacks by Ditsch
Planning / Implementation / Main components |
YORK Deutschland GmbH |
Refrigerant |
ammonia (NH3) |
System start-up |
1999 |
Ditsch, a wholesale bakery, sells specialties including salt pretzels, pizzas and croissants. To ensure that products are always fresh, the bakery supplies its branches with frozen raw products, which are baked on the premises as needed. |
|
Demands |
To ensure consistent top quality in the freezing and chilling of the pre-formed dough. |
Solution |
The production system uses both a low pressure (-40 ºC) and a medium pressure refrigeration cycle (-10 ºC). The refrigerant used is ammonia. The sensitive fermentation cooling and air conditioning is handled by an indirect refrigeration cycle using glycol water as a secondary refrigerant. Heat is recovered using plate heat exchangers, and can be used to heat service water. The use of ammonia makes this refrigeration process both environmentally friendly and economical. |
Technical data:
Type of facility |
pumped recirculation plant |
Refrigerant |
NH3 |
Refrigerant volume |
3,800 kg |
Secondary refrigerant |
Ethylene glycol / water |
Refrigeration plant |
|
Low-pressure stage: 2 ammonia screw compressors |
Model SAB 202 SM, at -40 ºC/-10 ºC Refrigerating capacity 490 kW, 2,950 RPM, drive motors 75 kW each, liquid separator 700 kW with 3 refrigerant pumps |
High-pressure stage: 2 ammonia screw compressors |
Model SAB 163 HF, at -10 ºC/+35 ºC Refrigerating capacity 1,240 kW, 2,950 RPM, drive motors 200 kW each, discharge gas desuperheater 130 kW, liquid separator 1,600 kW with 2 refrigerant pumps |
Condensers |
1,800 kW evaporative condenser, with section for cooling the 280 kW oil cooler glycol / water |
Heat recovery |
via the 280 kW oil cooler plate heat exchangers; used as service water |
Cooling consumers |
|
Low-pressure cycle (-40 ºC) |
180 kW cold store, continuous-flow freezer 1 x 170 kW, 1 x 120 kW, 1 x 114 kW, entry cooler 5 x 10 kW |
Medium-pressure cycle |
a variety of cooling units 100 kW, fermentation cooler 140 kW, 400 kW brine cooler plate heat exchanger, indirect cooling: product cooling, ice water production and air conditioning. |
Controls |
Visualised system on PC with BUS system for communication and data capture, microprocessor controls and monitoring Model UNISAB for the compressor |